kirloskar Generators

82.5 - 125 KVA
Prime Rating at rated rpm ( as per ISO8528)1
kVA
82.5
100
125
125HD

kW
66
80
100
100

Genset Model

KG1- 82.5WS
KG1- 100WS
KG1- 125WS
KG1-125WS HD

Frequency
Hz
50
50
50
50

Power factor
lagging
0.8
0.8
0.8
0.8

Voltage
V
415 3Ø
415 3Ø
415 3Ø
415 3Ø

Governing class (As per ISO 8528 Part-V)

G2
G3
G3
G3

Noise level
dBA
< 75
< 75
< 75
< 75

Fuel Consumption*
At 100 % Load
Ltrs/hr
18.8
21.9
27.4
29.6

At 75 % Load
13.8
16.9
20.2
22.4

At 50 % Load
9.9
12.2
15.3
15.3

Fuel tank capacity
Ltrs
150
230
230
230

Overall dimensions of genset (L x W x H)^
mm
3200 x
1100 x
1595
3200 x
1300 x
1795
3200 x
1300 x
1795
3650 x
1350 x
1915

Dry weight of genset with canopy (approx..)^
Kg
1710
2040
2090
2450

Wet weight of genset with canopy (approx..)^
Kg
1840
2240
2290
2650

Electrical Battery starting voltage 
Volts-DC
12
12
12
12

ENGINE
Engine Model

4R1040TA G1
4K1080TA G2
4K1080TA G2
6R1080TA G1
Rated output (Prime Continuous rating as per
)
kW
74.8
114.7
114.7
114.7
HP
102
156
156
156
No. of cylinder 
Number
4
4
4
6
Cubic capacity 2
Ltrs
4.16
4.32
4.32
6.49
Bore x Stroke
mm
105 x 120
105 x 125
105 x 125
105 x 125
Rated Speed
RPM
1500
1500
1500
1500
Aspiration
NA/TC/TA
TA
TA
TA
TA
Lube Oil change period
hrs.
500
500
500
500
Lube oil Sump Capacity
Ltrs
10
18
18
12
Coolant Capacity
Ltrs
24
21
21
28
ALTERNATOR
Insulation Class

Class H
Alternator Efficiency (at 100% load) 0.8 pf**
%
91.4
92.0
92.5
92.5
Max Voltage Dip at Full Load 0.8 pf Lag

< 20 %
< 20 %
< 20 %
< 20 %
Max Time to build up rated voltage at Rated RPM
sec
< 5 sec provided engine reach the rated speed
For intermediate ratings, kindly contact nearest KOEL office
Notes
^ Tolerances Apply
*With 0.845 Specific Gravity of diesel ( 5 % Tolerance )
** Efficiency of Alternator as per standards IS 4722 and IEC 34-1 For Site Conditions other than standard operating conditions consult KOEL for available prime power.

Comments